Abstract

The last decade has noticed the rapidly growing use of medium-voltage (MV) low-power instrument transformers (LPITs) which are based on low-power principles such as Rogowski coil and resistive or capacitive voltage dividers. These advanced technologies are being utilized also in applications such as energy and power quality metering where frequency response with accurate measurement of low and high harmonics is a key factor for proper opera­tion. This paper deals with accuracy requirements for harmo­nics and low frequencies as stated in IEC standards for LPITs introduced by the new IEC 61869 stan­dards family. This paper describes practical LPIT aspects which influence frequency response, sum­ma­rizes available testing methods and presents results of tests perfor­med on a wide range of LPITs. It focuses only on LPITs which do not involve digital data processing/transmission.