Forensic studies on 9 teardown power transformers - Correlation between DPv paper and 2-FAL and extrapolation to estimate the remaining useful lifetime of relative transformers in service
Loading...
Paper number
1187
Working Group Number
Conference name
CIRED 2019
Conference date
3-6 June 2019
Conference location
Madrid, Spain
Peer-reviewed
Yes
Short title
Convener
Authors
Ferreira, João Vasco, EDP Distribuição, Portugal
Carvalho, Cristina, EDP Distribuição, Portugal
Pinto Sá, Luís, EDP Distribuição, Portugal
Peixoto, Anabela, LABELEC, Portugal
Martins, Rui, LABELEC, Portugal
Carvalho, Cristina, EDP Distribuição, Portugal
Pinto Sá, Luís, EDP Distribuição, Portugal
Peixoto, Anabela, LABELEC, Portugal
Martins, Rui, LABELEC, Portugal
Abstract
This paper presents a study from EDP Distribuição
and LABELEC, whose purpose was to develop a methodology to estimate the
remaining useful lifetime (RUL) of 86 High Voltage (HV)/ Medium
Voltage (MV) power transformers in service, based on data from the DPv
(viscometric degree of polymerization) measurements of insulation paper of 9 HV/MV
power transformers intended for scrapping.We present the methodology developed during
the study and the final results.
Table of content
Keywords
Publisher
AIM
Date
2019-06-03
Published in
Permanent link to this record
https://cired-repository.org/handle/20.500.12455/333
http://dx.doi.org/10.34890/563
http://dx.doi.org/10.34890/563
ISSN
2032-9644
ISBN
978-2-9602415-0-1