Typical harmonic levels and spectra with low-voltage customers
Loading...
Paper number
366
Working Group Number
Conference name
CIRED 2019
Conference date
3-6 June 2019
Conference location
Madrid, Spain
Peer-reviewed
Yes
Short title
Convener
Authors
Bollen, Math, LuleĂĄ University of Technology, Sweden
Gil de Castro, Aurora, University of Cordoba, Spain
Rönnberg, Sarah , Luleå University of Technology, Sweden
Gil de Castro, Aurora, University of Cordoba, Spain
Rönnberg, Sarah , Luleå University of Technology, Sweden
Abstract
This paper presents levels of harmonic voltage distortion with low-voltage customers during 2017 and 2018. Measurements were obtained over a period between one hour and one day per location. Results are presented for the harmonics in the phase-to-neutral voltage at 163 locations; the highest 10-minute values per location have been used for presenting the results. For harmonics in the neutral-to-ground voltage, 1-second values at 88 locations have been used. The harmonic levels showed to be well below the limits in EN 50160 and IEC 61000-2-2 for almost all locations and for all harmonics with exception of harmonics 9, 15 and 21. The dominating frequencies at most locations are harmonics 5 and 7.
Table of content
Keywords
Publisher
AIM
Date
2019-06-03
Published in
Permanent link to this record
https://cired-repository.org/handle/20.500.12455/818
http://dx.doi.org/10.34890/1031
http://dx.doi.org/10.34890/1031
ISSN
2032-9644
ISBN