Utilization of a mixture of CTs and current sensors in line differential protection applications

Loading...
Thumbnail Image

Paper number

292

Working Group Number

Conference name

CIRED 2019

Conference date

3-6 June 2019

Conference location

Madrid, Spain

Peer-reviewed

Yes

Short title

Convener

Authors

Raipala, Ontrei, ABB Oy, Finland
Hovila, Petri, ABB Oy, Finland
Leminen, Janne, ABB Oy, Finland
Farughian, Amir, University of Vaasa, Finland
Memon, Aushiq, University of Vaasa, Finland
Kauhaniemi, Kimmo, University of Vaasa, Finland

Abstract

The popularity of Rogowski sensors is increasing due to their advantages over conventional CTs. Consequently, network utilities may sometimes end up facing a question whether it would be possible to use line differential protection on a line where the current measurements at the local end are based on CTs, whereas, the remote end measurements are based on current sensors. The main challenge in the use of such a combination in line differential protection applications is that while CTs may saturate, Rogowski sensors do not. Such issues were studied in a hardware-in-the-loop simulation setup. Based on the studies conducted, it appears that the use of mixture of CTs and current sensors for line differential protection applications is a feasible option provided that the CTs are properly dimensioned and that the protection settings are carefully chosen.

Table of content

Keywords

Publisher

AIM

Date

2019-06-03

Permanent link to this record

https://cired-repository.org/handle/20.500.12455/808
http://dx.doi.org/10.34890/1026

ISSN

2032-9644

ISBN