Mitigation of Faults in Grid-Connected Single Machine Brushless Double-Fed Induction Generator
Paper number
425Conference name
CIRED 2019Conference date
3-6 June 2019Conference location
Madrid, SpainPeer-reviewed
YesMetadata
Show full item recordAuthors
Nashed, Maged, Electronics Research Institute, EgyptEskander, Mona, Electronics Research Institute, Egypt
Saleh, Mahmoud, Electronics Research Institute, Egypt
Abstract
The effect of three-phase grid fault on the performance of a wind-driven single machine-brushless double fed induction generator (SM-BDFIG) is investigated. The fault-ride-through (FRT) of the grid-connected SM-BDFIG is then studied when installing a Static Synchronous Compensator (STATCOM) between the grid and the generator. Recovery from the grid fault before installing the STATCOM is studied and compared to the generation system recovery with installed STATCOM. The performances of the stator and rotor currents, stator and rotor voltages, electric torque, active power, reactive power, and battery pack voltage and current are presented for both cases. The total harmonic distortion (THD) of stator and rotor voltages and currents are also presented and compared. Results proved the faster recovery from grid faults, the continuity of currents and voltages, and the continuity of active power supplied to the grid when installing the STATCOM. However, slightly higher THD took place in the stator and rotor voltages and currents due to the switching pattern of the STATCOM.Publisher
AIMDate
2019-06-03Published in