    Two Years of Battery Energy Storage System performance in automatic islanding in the Portuguese MV network

    Thumbnail
    View/Open
    CIRED 2019 - 1065.pdf (308.5Kb)
    Paper number
    1065
    Conference name
    CIRED 2019
    Conference date
    3-6 June 2019
    Conference location
    Madrid, Spain
    Peer-reviewed
    Yes
    Metadata
    Show full item record
    Authors
    Neves, André, EDP Distribuição, Portugal
    Falcão, André, EDP Distribuição, Portugal
    Louro, Miguel, EDP Distribuição, Portugal
    Terras, José Manuel, EDP Distribuição, Portugal
    Almeida, Bernardo, EDP Distribuição, Portugal
    Veríssimo, Miguel, EDP Distribuição, Portugal
    Ferreira Pinto, José, EDP Distribuição, Portugal
    Damásio, José, Siemens S.A., Portugal
    Abstract
    Energy Storage Systems (ESS) have been an important topic among DSOs, due to the flexibility that it provides to the grid. EDP Distribuição (EDPD), the main Portuguese DSO, has partnered up with a well-known manufacturer, SIEMENS, a research center, INESC I&D, and a local University, University of Évora, to install a Medium Voltage (MV) Storage facility that is able to work in both grid connected and islanding mode with the University secondary substation. To achieve this, the MV client University of Évora is connected to the grid in such a way as to enable both operating modes. The ESS, which contains lithium batteries modules, has a rated Power of 472kVA and a capacity of 360 kWh. The ESS was built to be modular and moveable so it can be installed in other nodes of the grid or upgraded with more power and capacity.The ESS automatically reconnects to the grid after the voltage returns to normal operation values ensuring an almost continuous operation. In this study, the authors will present the knowledge acquired in the last 2 years of experience operating a MV Storage unit in the Portuguese grid. During this time, the ESS system went into islanding mode for several times due to unplanned grid outages, which constitutes a good baseline for the ESS behaviour assessment regarding islanding. These real cases of successful and unsuccessful islanding operation will be the focus of this paper as well as an analysis on the motives for the few unsuccessful cases.
    Publisher
    AIM
    Date
    June 2019
    Published in
    • CIRED 2019 Conference
    ISSN
    2032-9644
    ISBN
    978-2-9602415-0-1

    Browse

    All of CIRED RepositoryCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

    My Account

    Admin LoginRegister

    DSpace software copyright © 2002-2019  DuraSpace
    Contact Us | Send Feedback
    DSpace Express is a service operated by 
    Atmire NV