dc.description.abstract | Due to today´s increased demands on grid
operation management, new methods for earth fault localization and detection
are needed. The fault localization should be performed as quickly as possible
and under the condition, that the fault current at the fault location will not
be significantly increased. In today´s meshed compensated networks with
increased length, only the transient relays work correctly. But these relays
give a signalization only during the beginning of an earth fault. They are not
able to give correct information after a change of the network-configuration.
During the steady state of the earthfault more or less all existing methods
cause problems. The new proposed method is based on
injection of a zero-sequence current during an earthfault by tuning the
Petersen-Coil. The relays have to use a
simple evaluation of the zero-sequence current in the complex plane. Using this method, an identification of the
faulty feeder as well as a distance estimation up to the earthfault location is
possible. This paper will present the
first results of this evaluation. | |
dc.language.iso | en | |
dc.publisher | AIM | |
dc.relation.ispartofseries | CIRED Conference Proceedings | |
dc.title | New method for identification and localisation of an earthfault in compensated networks | |
dc.type | Conference Proceedings | |
dc.description.conferencelocation | Madrid, Spain | |
dc.relation.ispart | Proc. of the 25th International Conference on Electricity Distribution (CIRED 2019) | |
dc.contributor.detailedauthor | DRUML, Gernot, Sprecher Automation GmbH, Germany | |
dc.contributor.detailedauthor | SKRBINJEK, Oliver, Energie Steiermark, Austria | |
dc.contributor.detailedauthor | Schmidt, Uwe, University Zittau, Germany | |
dc.contributor.detailedauthor | Frowein, Karla, TU-Dresden, Germany | |
dc.contributor.detailedauthor | Schegner, Peter, Technische Universitaet Dresden, Germany | |
dc.date.conferencedate | 3-6 June 2019 | |
dc.description.peerreviewed | Yes | |
dc.title.number | 65 | |
dc.description.openaccess | Yes | |
dc.contributor.country | Germany | |
dc.contributor.country | Austria | |
dc.contributor.country | Germany | |
dc.contributor.country | Germany | |
dc.contributor.country | Germany | |
dc.description.conferencename | CIRED 2019 | |
dc.contributor.affiliation | Sprecher Automation GmbH | |
dc.contributor.affiliation | Energie Steiermark | |
dc.contributor.affiliation | University Zittau | |
dc.contributor.affiliation | TU-Dresden | |
dc.contributor.affiliation | Technische Universitaet Dresden | |
dc.description.session | Operation, control and protection | |